IO Mapping

nXPlc has no process I/O on board: plant inputs and outputs come from the neXo modules on the bus, under the IO-Locali node. The channels of the IO node, described here, do not drive actuators and do not read plant sensors: they tell you how the board is doing, and let you show it to whoever is looking at it.

The rest goes through the CAN bus and the local I/O modules.

ChannelParameter IDTypeMeaning
PWR_FAIL1000BIT24 V present — active low: FALSE when the supply fails
VCAP_READY1001BITsupercaps charged
TEMPERATURE5000REALRP2350 die temperature, in °C

PWR_FAIL and VCAP_READY are the pair you shut down on: the first warns that the supply is failing, the second tells you whether you still have the energy to do something about it. They are hardware diagnostics, not process inputs — a comparator watches the 24 V rail and trips before the converter gives way.

TEMPERATURE is the sensor inside the microcontroller, not a process probe: it measures how hot the silicon runs, not the environment the board lives in.

ChannelParameter IDTypeDrives
LED_RUN2000BITgreen indicator DL6
LED_ERR2001BITred indicator DL7

The two indicators are bit channels, on or off.